WAGO I/O System 750
Process Image 39
750-637 Incremental Encoder Interfaces
Manual
Version 1.6.1
Public
Table 30: Status Byte S1, All Versions, Except 750-637/000-004
Status Byte S1
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
0
N2
N1
StaN2
StaN1
MapPZD
MapPZD
MapPZD
Coding of Process Data
MapPZD
Coding of Process Data
StaN1
Status Cam Output 1
0:
Cam output 1 is not set
1:
Cam output 1 is set
StaN2
Status Cam Output 2
0:
Cam output 2 is not set
1:
Cam output 2 is set
N1
Cam Window 1
Bit is set when:
Lower comparison value N1_LO ≤ counter value ≤ upper
comparison value N1_HI
N2
Cam Window 2
Bit is set when:
Lower comparison value N2_LO ≤ counter value ≤ upper
comparison value N2_HI
0
Reserved
0
Reserved
Table 31: Status Byte S1, Version 750-637/000-004
Status Byte S1
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
0
N2_F1
N1_F1
N2_F2
N1_F2
Set Cam_
Ack
MapPZD
MapPZD
Coding of Process Data
Set Cam_Ack
Collective and Ack Bit for All Cam Set Requests
Bit is set when: One or more request bists 2,3,4 or 5 are set by the
control byte.
N1_F2
Cam 1, Window 2
Bit is set when:
Lower comparison value N1F2_LO < counter value <
upper comparison value N1F2_HI and cams enabled
(C1.6) and field voltage present (S0.6=0)
N2_F2
Cam 2, Window 2
Bit is set when:
Lower comparison value
N2F2_LO < counter value <
upper comparison value N2F2_HI and cams enabled
(C1.6) and field voltage present (S0.6=0)
N1_F1
Cam 1, Window 1
Bit is set when:
Lower comparison value N1F1_LO < counter value <
upper comparison value N1F1_HI and cams enabled
(C1.6) and field voltage present (S0.6=0)
N2_F1
Cam 2, Window 1
Bit is set when:
Lower comparison value N2F1_LO < counter value <
upper comparison value N2F1_HI and cams enabled
(C1.6) and field voltage present (S0.6=0)
0
Reserved
0
Reserved