![WAGO 750-637 Manual Download Page 36](http://html1.mh-extra.com/html/wago/750-637/750-637_manual_3167294036.webp)
36 Process Image
WAGO I/O System 750
750-637 Incremental Encoder Interfaces
Manual
Version 1.6.1
Public
Table 26: MapPZD, All Versions, Except 750-637/000-004
MapPZD (Control Byte C1/ Status Byte S1, Bit 0 and Bit 1)
Bit 1
Bit 0
Coding of Process Data
0
0
Count value
0
1
Latch value
1
0
Rate in increments per milliseconds
1
1
Set value
With Version 750-637/000-004, the following process data is displayed as a
function of bit 0 in control byte C1 (see Table “MapPZD, Verstion 750-637/000-
004”):
• Counter value
• Latch value
The setting is mirrored in bit 0 of status byte S1.
Table 27: MapPZD, Version 750-637/000-004
MapPZD (Control Byte C1/ Status Byte S1, Bit 0)
Bit 0
Coding of Process Data
0
Count value
1
Latch value