WAGO-I/O-SYSTEM 750
Connect Devices
31
750-530 8DO 24V DC 0.5A
Manual
Version 1.2.0
Pos: 77 /All e Seri en (Allgemei ne Module)/Ü berschriften für alle Serien/Anschließ en/Ger äte anschließen - Ü berschrift 1 @ 3\mod_1234172889468_21.docx @ 27460 @ 1 @ 1
6
Connect Devices
Pos: 78 /Serie 750 ( WAGO-I/O-SYST EM)/Anschli eßen/Leiter an C AGE C LAM P anschli eßen ( allgemei n) - Überschrift 2 und Text @ 3\mod_1225448660171_21.docx @ 24928 @ 2 @ 1
6.1
Connecting a Conductor to the CAGE CLAMP
®
The WAGO CAGE CLAMP
®
connection is appropriate for solid, stranded and
finely stranded conductors.
Only connect one conductor to each CAGE CLAMP
®
!
Only one conductor may be connected to each CAGE CLAMP
®
.
Do not connect more than one conductor at one single connection!
If more than one conductor must be routed to one connection, these must be
connected in an up-circuit wiring assembly, for example using WAGO feed-
through terminals.
Exception:
If it is unavoidable to jointly connect 2 conductors, then you must use a ferrule to
join the wires together. The following ferrules can be used:
Length:
8 mm
Nominal cross section
max.
:
1 mm
2
for 2 conductors with 0.5 mm
2
each
WAGO product:
216-103 or products with comparable properties
1.
For opening the CAGE CLAMP
®
insert the actuating tool into the opening
above the connection.
2.
Insert the conductor into the corresponding connection opening.
3.
For closing the CAGE CLAMP
®
simply remove the tool. The conductor is
now clamped firmly in place.
Figure 10: Connecting a Conductor to a CAGE CLAMP
®
Pos: 79 /D okumentation allgemei n/Glieder ungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1