background image

 

 

750-523 [1 DO AC 230 V 16 A/Relay 1a/Pot. free] 

•  

 

 

View 

WAGO-I/O-SYSTEM 750 
I/O Modules 

2 I/O Modules 

2.1  Digital Output Modules 

2.1.1 750-523 [1 DO AC 230 V 16 A/Relay 1a/Pot. free] 

1-Channel Relay Output Module AC 230 V, 16 A, 
isolated outputs, 1 make contact, bistable, manual operation 

2.1.1.1 View 

L

L

750-523

DO DO

0

1

AUTO

HAND

HAND

Status
manual mode

Manual / automatic

Data contacts

Manual operationl

Switched status

Power jumper contacts

L
DO

N

 

Fig. 2.1.1-1: 2-Channel Relay Output Module 750-523 

g052300e 

2.1.1.2 Description 

A connected actuator or load is switched via the relay output module. 
The 24 V supply is derived from the power jumper contacts to trigger the re-
lays. 

The module has one output channel and enables the connection of one or two 
actuators. 
The signal output DO has two parallel connections so that an actuator can be 
wired using one or two conductors of cross section > 2.5 mm². It is also possi-
ble to connect two actuators in parallel.   

The module is equipped with an isolated contact relay so that only the connec-
tion points of the relay contacts are available on the fieldside. 

Due to the isolated contacts, it is possible, for example, to connect several re-
lays in series by grouping these modules. 

Summary of Contents for 750-523

Page 1: ...Fieldbus Independent I O Modules 1 DO AC 230 V 16 A Relay 1a Pot free 750 523 Manual Version 1 0 5...

Page 2: ...571 8 87 5 55 Fax 49 0 571 8 87 85 55 E Mail support wago com Every conceivable measure has been taken to ensure the correctness and com pleteness of this documentation However as errors can never be...

Page 3: ...er Notation 5 1 4 Safety Notes 6 1 5 Scope 6 2 I O Modules 7 2 1 Digital Output Modules 7 2 1 1 750 523 1 DO AC 230 V 16 A Relay 1a Pot free 7 2 1 1 1 View 7 2 1 1 2 Description 7 2 1 1 3 Display Elem...

Page 4: ...are always named without referring to patent rights The existence of such rights can therefore not be ruled out 1 1 2 Personnel Qualification The use of the product detailed in this manual is exclusiv...

Page 5: ...ESD Electrostatic Discharge Warning of damage to the components by electrostatic discharge Observe the precautionary measure for handling components at risk Note Routines or advice for efficient use...

Page 6: ...s to be regarded Do not use any contact spray The spray may impair the functioning of the contact area The WAGO I O SYSTEM 750 and its components are an open system It must only be assembled in housin...

Page 7: ...2 Description A connected actuator or load is switched via the relay output module The 24 V supply is derived from the power jumper contacts to trigger the re lays The module has one output channel a...

Page 8: ...stem requiring a 24 V power supply fed in via the internal power jumper contacts of an adjacent supply module In this operating mode manual status transitions which may occur via the red manual operat...

Page 9: ...0 476 2 DI DC 10 V up to version number 3005 The output module has 24 V and 0 V built in power jumper contacts The 24 V power supply is used to trigger the relays The module is powered using an adjace...

Page 10: ...ay Elements g052302x LED Channel Designation State Function off Operating mode automatic yellow flashing 1 Status manual operation on Operating mode manually operated LED Channel Designation State Fun...

Page 11: ...A Contact material AgSnO2 Mechanical life 106 switching operations Isolation 1 5 kVeff System Field 2 5 kV rated surge voltage overvoltage category III Internal bit width 2 Bit In Manual status 2 Bit...

Page 12: ...d 1 000 W 2 000 W Mercury arc sodium discharge lamp parallel compensated 1 000 W 70 F 2 000 W 140 F Dulux lamp not compensated 800 W 1 600 W Dulux lamp parallel compensated 560 W 70 F 1 100 W 140 F Mo...

Page 13: ...Value Graph of the Relay WAGO I O SYSTEM 750 I O Modules 2 1 1 7 Load Limiting Value Graph of the Relay 100 0 1 1 10 10 20 30 50 200 300 0 5 5 16 20 Direct Current A Direct Voltage V Fig 2 1 1 5 Direc...

Page 14: ...fective Attenuation Advantages Disadvantages Diode UD Load g051211e long yes UD no Advantages easy implementation cost effective reliable uncritical dimensioning low induction voltage Disadvantages at...

Page 15: ...Digital Output Modules 15 Contact Protective Circuit for Relay Modules WAGO I O SYSTEM 750 I O Modules...

Page 16: ...WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastra e 27 D 32423 Minden Phone 05 71 8 87 0 Fax 05 71 8 87 1 69 E Mail info wago com Internet http www wago com...

Reviews: