WAGO-I/O-SYSTEM 750
Device Description
13
750-513 2DO 230V AC 2.0A/ Relay 2NO/ Potential Free
Manual
Version 1.2.2
Pos: 19 /All e Seri en (Allgemei ne Module)/Ü berschriften/N eue Ü berschriften/Ebene 1Ger ätebeschrei bung - Ü berschrift 1 @ 3\mod_1233756084656_21.docx @ 27096 @ 1 @ 1
3
Device Description
Pos: 20.1.1 /Serie 750 (WAGO-I/O-SYST EM)/Gerätebeschrei bung/Ei nlei tung/Anwendung/D O/Anwendung 750- 05xx DO Rel ais @ 5\mod_1246611276875_21.docx @ 36561 @ @ 1
The 750-513 Digital Output Module transmits binary control signals from the
automation device to the connected actuators (e.g., solenoid valves, contactors,
transmitters, relays or other electrical loads).
Pos: 20.1.2 /Serie 750 (WAGO-I/O-SYST EM)/Gerätebeschrei bung/Ei nlei tung/I/O-Beschrei bung/DO/I/O-Beschrei bung 750-0513 2 D O 2-Leiter (DO und N) @ 23\mod_1440514658305_21.docx @ 190212 @ @ 1
The I/O module has 2 output channels, providing for direct connection of
actuators equipment with protection classes II and III.
The actuators can be wired directly to the CAGE CLAMP
®
connectors DO 1 and
to an external N potential or DO2 and an external N potential. An external
potential of 230 VAC or 30 VDC can be applied to relay contacts 13 and 23.
Pos: 20.1.3 /Serie 750 (WAGO-I/O-SYST EM)/Gerätebeschrei bung/Ei nlei tung/I/O-Beschrei bung/Allgemein/Ver weis auf Kapi tel " Anschlüsse" @ 8\mod_1276775378035_21.docx @ 57956 @ @ 1
The assignment of the connections is described in the “Connectors” section.
Pos: 20.1.4 /Serie 750 (WAGO-I/O-SYST EM)/Gerätebeschrei bung/Ei nlei tung/I/O-Beschrei bung/Allgemein/Ver weis auf Kapi tel " Geräte anschli eß en" > "Anschlussbeispi el(e)" @ 5\mod_1246015203281_21.docx @ 36298 @ @ 1
Connection examples are shown in section “Connecting Devices” > … >
“Connection Example(s)”.
Pos: 20.1.5 /Serie 750 (WAGO-I/O-SYST EM)/Wichtige Erläuterungen/Sicherheits- und sonstige Hinweise/Achtung/Achtung: D O Induktionsspannungsbegrenzung Elektr oni k @ 3\mod_1233815757507_21.docx @ 27153 @ @ 1
Limit all induced voltage!
The electronic components of the I/O module can be damaged by the induced
voltage produced when inductive loads are de-activated.
An appropriate protection circuit, e.g., a recovery diode, must be installed in
parallel to the load to limit this induced voltage.
Pos: 20.1.6 /Serie 750 (WAGO-I/O-SYST EM)/Gerätebeschrei bung/Ei nlei tung/I/O-Beschrei bung/DO/I/O-Beschrei bung 750-0513 @ 5\mod_1246614814593_21.docx @ 36580 @ @ 1
</dg_
The I/O module contains 2 make-contact, potential-free relays. This means that
only the connecting points for the relay contacts are available at the field side so
that different voltages can be applied independently to both make contacts.
The floating contacts also enable, for example, series connection of both relays, or
series connection of several relays when the I/O modules are set up in blocks.
When a relay is closed, the potential applied at 13 or 23 is routed to the associated
second relay contact 14 or 24.
Pos: 20.1.7 /Serie 750 (WAGO-I/O-SYST EM)/Gerätebeschrei bung/Ei nlei tung/I/O-Beschrei bung/DO/I/O-Beschrei bung 750-05xx Ansteuerung der R el ais (Interne Systemspannung) @ 5\mod_1246861676649_21.docx @ 36599 @ @ 1
The internal system voltage is used to trigger the relays.
Pos: 20.1.8 /Serie 750 (WAGO-I/O-SYST EM)/Gerätebeschrei bung/Ei nlei tung/LED-Anzeige/LED Zustand R elais @ 5\mod_1246862048946_21.docx @ 36603 @ @ 1
The switching status of the two relays is indicated via green status LEDs.
Pos: 20.1.9 /Serie 750 (WAGO-I/O-SYST EM)/Gerätebeschrei bung/Ei nlei tung/LED-Anzeige/Ver weis auf Kapitel "Anzeigeelemente" @ 5\mod_1246010525000_21.docx @ 36194 @ @ 1
The meaning of the LEDs is described in the “Display Elements” section.
Pos: 20.1.10 /Serie 750 ( WAGO-I/O- SYST EM)/Wichtig e Erl äuter ung en/Sicher hei ts- und sonstige Hi nweise/Hinweis/Hi nweis: Potential einspeiseklemme für Vari ante /000-001 ei nsetzen! (nur LK für Er de bzw. keine LK) @ 18\mod_1393918443397_21.docx @ 146952 @ @ 1
Use the supply module!
The standard version of the 750-513 I/O module is equipped with an integrated
power contact for relaying the ground potential, while the version 750-513/000-
001 does not come equipped with a power contact. When required, use a power
supply module for the field-side supply of the following I/O modules.
Pos: 20.1.11 /Serie 750 ( WAGO-I/O- SYST EM)/Gerätebeschr eibung/Einl eitung/Versorgung/Anordnung unter Ber ücksichtigung der Leistungskontakte beliebig @ 3\mod_1233756233468_21.docx @ 27099 @ @ 1