28 Process Image
WAGO I/O System 750
750-506 2DO 24V DC 0.5A/ diagnostics
Manual
Version 1.2.1
Public
Pos: 61 /All e Seri en (Allgemei ne Module)/Ü berschriften/Ebene 1/Prozessabbild - Ü berschrift 1 @ 4\mod_1240983067828_21.docx @ 31942 @ 1 @ 1
4
Process Image
Pos: 62 /Serie 750 ( WAGO I/O SYSTEM)/Prozessabbild Lokalbus/Hinweis: Prozessabbil dmappi ng abhängig von F BK/PFC , ohne Status-/Contr olbyte @ 6\mod_1256126797251_21.docx @ 43340 @ @ 1
Mapping of process data in the process image of fieldbus systems
The representation of the process data of some I/O modules or their variants in
the process image depends on the fieldbus coupler/controller used. Please take
this information from the section “I/O Modules” included in the description
concerning the process image of the corresponding coupler/controller.
Pos: 63 /Serie 750 ( WAGO I/O SYSTEM)/Prozessabbild Lokalbus/DO/Prozessabbil d 75x- 506 @ 31\mod_1523621344210_21.docx @ 481879 @ @ 1
Table 16: Output Bits
Bit 3
Bit 2
Bit 1
Bit 0
x
x
DO 2
DO 1
DO 1
Signal state DO 1 – Digital output channel 1
DO 2
Signal state DO 2 – Digital output channel 2
x
Not in use
Table 17: Input Bits
Bit 3
Bit 2
Bit 1
Bit 0
DIAG 2
DIAG 1
DIAG n
00
b
Normal operation, output DO n follows the output bit.
01
b
If output is active:
a) No load connected
If output not active:
b) Short circuit a24 V
10
b
c) Short circuit to GND or
d) Overtemperature at overload
11
b
e) Undervoltage of the field supply