34 Process Image
WAGO-I/O-SYSTEM 750
750-496 8AI 0/4-20mA S.E.
Manual
Version
1.2.2
4.3.2.2 Sensor Type 4 … 20 mA
For the current measurement with sensor type 4 … 20 mA, the input range of
+4 … +20 mA is mapped to a value rage of 0 … +32767. The current
underranges and overranges refer to manufacturer range violations.
Table 20: Process Image, Sensor Type 4 … 20 mA, Two's Complement Representation
Input current
mA
Numeric value
Status
Byte
Hex.
Error LED
Binary
XFÜ
1)
Hex.
Dec.
< 1.0
'0000.0000.0000.0 011'
0x0003
3
0x60
ON
Wire break
3)
< 4.0
'0000.0000.0000.0 011'
0x0003
3
0x41
ON
Underrange
2)
4.0
'0000.0000.0000.0 000'
0x0000
0
0x00
OFF
5.6
'0000.1100.1100.0 000'
0x0CC8
3272
0x00
OFF
7.2
'0001.1001.1001.1 000'
0x1998
6552
0x00
OFF
8.8
'0010.0110.0110.0 000'
0x2660
9824
0x00
OFF
10.4
'0011.0011.0011.0 000'
0x3330
13104
0x00
OFF
12.0
'0011.1111.1111.1 000'
0x3FF8
16376
0x00
OFF
13.6
'0100.1100.1100.1 000'
0x4CC8
19656
0x00
OFF
15.2
'0101.1001.1001.1 000'
0x5998
22936
0x00
OFF
16.8
'0110.0110.0110.0 000'
0x6660
26208
0x00
OFF
18.4
'0111.0011.0011.0 000'
0x7330
29488
0x00
OFF
20.0
'0111.1111.1111.1 000'
0x7FF8
32760
0x00
OFF
Overrange
2)
'0111.1111.1111.1 011'
0x7FFB
32763
0x42
ON
> 20.0
Short circuit
3)
'0111.1111.1111.1 011'
0x7FFB
32763
0x50
ON
> 21.0
1)
Status bits: X: not used, F= error, Ü= overflow
2)
When underrange / overrange limit is ON
3)
When wire break / short circuit diagnostics is ON