200 Commissioning
WAGO-I/O-SYSTEM 750 XTR
750-495/040-00x 3-Phase Power Measurement Module 690 V
Manual
Version 1.2.0
8.3.3
“Neutral Conductor” Tab
On the “Neutral Conductor” tab, parameterize the application scaling for the
neutral conductor and specify the threshold for the peak value of Tamper Detect
(fault current detection).
Settings for Rogowski coils
If you are using Rogowski coils with the Rogowski version, user scaling cannot
be enabled. Thus, the transformation ratio is always 1:1. Otherwise, incorrect
measured values will result.
These settings apply to the neutral conductor and are written to the I/O module
when saved.
Figure 61: “Neutral Conductor” Tab