WAGO-I/O-SYSTEM 750
Appendix 111
750-494 3-Phase Power Measurement Module
Manual
Version 1.2.0
Table 34: Register 43
Register 43 – Observation interval, peak value measurement phase L1
Function
Data type
Access
Factory setting
Observation interval, peak value measurement,
phase L1
UINT
R/W
0 x 000 A
0 … 5:
-not permitted-
6 … 254: Number of half waves for measuring peak values.
≥255:
-not permitted-
Table 35: Register 44
Register 44 – Observation interval, peak value measurement phase L2
Function
Data type
Access
Factory setting
Observation interval, peak value measurement,
Phase 2
UINT
R/W
0 x 000 A
0 … 5:
-not permitted-
6 … 254: Number of half waves for measuring peak values.
≥255:
-not permitted-
Table 36: Register 45
Register 45 – Observation interval, peak value measurement phase L3
Function
Data type Access
Factory setting
Observation interval, peak value measurement,
phase L3
UINT
R/W
0 x 000 A
0 … 5:
-not permitted-
6 … 254: Number of half waves for measuring peak values.
≥255:
-not permitted-
Table 37: Register 46
Register 46 – Storing interval for energy values
Function
Data type
Access
Factory setting
Storing interval for energy values,
Resolution: 1 second
UINT
R/W
0x003C (60s)
0 … 59:
-not permitted-
60 … 255: Time in seconds up to automatic storing of energy values.
≥256:
-not permitted-