![WAGO 750-489 Manual Download Page 84](http://html1.mh-extra.com/html/wago/750-489/750-489_manual_868450084.webp)
84 Process Image
WAGO-I/O-SYSTEM 750
750-489 4AI RTD/TC/Strain Gauge Ex i
Manual
Version 1.1.0, valid from FW Version 02
4.6.4.2 S5-FB250 Format/Kelvin
The temperature values are displayed at a resolution of one digit per 0.1 K.
The status information is represented in bit 0 to bit 2 and the digitized measured
value in bit 3 to bit 15.
Table 93: Temperature Measurement Setting with High Resolution Option – S5-FB250 Format/Kelvin
Temperature
[K]
Numeric Value
Status
Byte,
Hex.
Error
LED
Range
Binary
XFÜ
1)
Hex.
Dec.
≤ 213
.1
'1000.0000.0000.0 010'
0x8002
-32766
0x50
On
Underflow
213.2
'0100.0010.1001.1 001'
0x4299
17049
0x41
On
Underrange
223.1
'0100.0101.1011.1 001'
0x45B9
17849
223.2
'0100.0101.1011.1 000'
0x45B8
17848
0x00
Off
Nominal
range
327.0
'0110.0110.0011.0 000'
0x6630
26160
327.1
'0110.0110.0011.1 001'
0x6639
26169
0x42
On
Overrange
327.5
'0110.0110.0101.1 001'
0x6659
26201
≥ 327
.6
'0111.1111.1111.1 010'
0x7FFA
32762
0x60
On
Overflow
1)
Status bits: X= not used, F= error, Ü= overflow
Table 94: Type C TC Setting with High Resolution Option – S5-FB250 Format/Kelvin
Temperature
[K]
Numeric Value
Status
Byte,
Hex.
Error
LED
Range
Binary
XFÜ
1)
Hex.
Dec.
≤ 263
.1
'1000.0000.0000.0 010'
0x8002
32766
0x50
On
Underflow
263.2
'0101.0010.0011.1 001'
0x5239
21049
0x41
On
Underrange
273.1
'0101.0101.0101.1 001'
0x5559
21849
273.2
'0101.0101.0101.1 000'
0x5558
21848
0x00
Off
Nominal
range
327.0
'0110.0110.0011.0 000'
0x6630
26160
327.1
'0110.0110.0011.1 001'
0x6639
26169
0x42
On
Overrange
327.5
'0110.0110.0101.1 001'
0x6659
26201
≥ 327
.6
'0111.1111.1111.1 010'
0x7FFA
32762
0x60
On
Overflow
1)