4.6.3.3 TC Type C – Standard Format/Kelvin
Table 77: TC Type C Setting – Standard Format/Kelvin
Temperature
[K]
Numeric Value
Status
Byte,
Hex.
Error
LED
Range
Binary
Hex.
Dec.
≤ 248
.1
'1000.0000.0000.0000'
0x8000 -32768
0x50
On
Underflow
248.2
'0000.1001.1011.0010'
0x09B2
2482
0x41
On
Underrange
273.1
'0000.1010.1010.1011'
0x0AAB
2731
273.2
'0000.1010.1010.1100'
0x0AAC
2732
0x00
Off
Nominal
range
2588.2
'0110.0101.0001.1010'
0x651A 25882
2588.3
'0110.0101.0001.1011'
0x651B 25883
0x42
On
Overrange
2613.2
'0110.0110.0001.0100'
0x6614
26132
≥ 2613
.3
'0111.1111.1111.1111'
0x7FFF 32767
0x60
On
Overflow
4.6.3.4 TC Type C – S5-FB250 Format/Kelvin
Table 78: TC Type C Setting – S5-FB250 Format/Kelvin
Temperature
[K]
Numeric Value
Status
Byte,
Hex.
Error
LED
Range
Binary
XFÜ
1)
Hex.
Dec.
≤ 247
.0
'1000.0000.0000.0 010'
0x8002
-32766
0x50
On
Underflow
248.0
'0000.0111.1100.0 001'
0x07C1
1985
0x41
On
Underrange
272.0
'0000.1000.1000.0 001'
0x0881
2177
273.0
'0000.1000.1000.1 000'
0x0888
2184
0x00
Off
Nominal
range
2588.0
'0101.0000.1110.0 000'
0x50E0
20704
2589.0
'0101.0000.1110.1 001'
0x50E9
20713
0x42
On
Overrange
2613.0
'0101.0001.1010.1 001'
0x51A9
20905
≥ 2614
.0
'0111.1111.1111.1 010'
0x7FFA
32762
0x60
On
Overflow
1)
Status bits: X= not used, F= error, Ü= overflow