![WAGO 750-489 Manual Download Page 63](http://html1.mh-extra.com/html/wago/750-489/750-489_manual_868450063.webp)
WAGO-I/O-SYSTEM 750
Process Image 63
750-489 4AI RTD/TC/Strain Gauge Ex i
Manual
Version 1.1.0, valid from FW Version 02
4.5.3.3 TC Type C – Standard Format/Fahrenheit
Table 53: TC Type C Setting – Standard Format/Fahrenheit
Temperature
[°F]
Numeric Value
1)
Status
Byte,
Hex.
Error
LED
Range
Binary
Hex.
Dec.
≤
-13.1
'1000.0000.0000.0000'
0x8000 -32768
0x50
On
Underflow
-13.0
'1111.1111.0111.1110'
0xFF7E
-130
0x41
On
Underrange
31.9
'0000.0001.0011.1111'
0x013F
319
32.0
'0000.0001.0100.0000'
0x0140
320
0x00
Off
Nominal
range
3270.0
'0111.1111.1011.1100'
0x7FBC 32700
3270.1
'0111.1111.1011.1101'
0x7FBD 32701
0x42
On
Overrange
3275.0
'0111.1111.1110.1110'
0x7FEE 32750
≥ 3275.1
'0111.1111.1111.1111'
0x7FFF 32767
0x60
On
Overflow
1)
Process values below 0 are represented in binary form as the two’s complement.
4.5.3.4 TC Type C – S5-FB250 Format/Fahrenheit
Table 54: TC Type C Setting – S5-FB250 Format/Fahrenheit
Temperature
[°F]
Numeric Value
Status
Byte,
Hex.
Error
LED
Range
Binary
XFÜ
1)
Hex.
Dec.
≤
-14.0
'1000.0000.0000.0 010'
0x8002
-32766
0x50
On
Underflow
-13.0
'1111.1111.0011.1 001'
0xFF99
-103
0x41
On
Underrange
31.0
'0000.0000.1111.1 001'
0x00F9
249
32.0
'0000.0001.0000.0 000'
0x0100
256
0x00
Off
Nominal
range
3270.0
'0110.0110.0011.0 000'
0x6630
26160
3271.0
'0110.0110.0011.1 001'
0x6639
26169
0x42
On
Overrange
3275.0
'0110.0110.0101.1 001'
0x6659
26201
≥ 3276.0
'0111.1111.1111.1 010'
0x7FFA
32762
0x60
On
Overflow
1)
Status bits: X= not used, F= error, Ü= overflow