![WAGO 750-489 Manual Download Page 56](http://html1.mh-extra.com/html/wago/750-489/750-489_manual_868450056.webp)
56 Process Image
WAGO-I/O-SYSTEM 750
750-489 4AI RTD/TC/Strain Gauge Ex i
Manual
Version 1.1.0, valid from FW Version 02
4.4.3.15 TC Type T – Standard Format/Celsius
Table 41: TC Type T – Standard Format/Celsius
Temperature
[°C]
Numeric Value
1)
Status
Byte,
Hex.
Error
LED
Range
Binary
Hex.
Dec.
≤
-225.1
'1000.0000.0000.0000'
0x8000 -32768
0x50
On
Underflow
-225.0
'1111.0111.0011.0110'
0xF736
-2250
0x41
On
Underrange
-200.1
'1111.1000.0010.1111'
0xF82F
-2001
-200.0
'1111.1000.0011.0000'
0xF830
-2000
0x00
Off
Nominal
range
400.0
'0000.1111.1010.0000'
0x0FA0
4000
400.1
'0000.1111.1010.0001'
0x0FA1
4001
0x42
On
Overrange
425.0
'0001.0000.1001.1010'
0x109A
4250
≥ 425.1
'0111.1111.1111.1111'
0x7FFF 32767
0x60
On
Overflow
1)
Process values below 0 are represented in binary form as the two’s complement.
4.4.3.16 TC Type T – S5-FB250 Format/Celsius
Table 42: TC Type T Setting – S5-FB250 Format/Celsius
Temperature
[°C]
Numeric Value
Status
Byte,
Hex.
Error
LED
Range
Binary
XFÜ
1)
Hex.
Dec.
≤
-226.0
'1000.0000.0000.0 010'
0x8002
-32766
0x50
On
Underflow
-225.0
'1111.1000.1111.1 001'
0xF8F9
-1799
0x41
On
Underrange
-201.0
'1111.1001.1011.1 001'
0xF9B9
-1607
-200.0
'1111.1001.1100.0 000'
0xF9C0
-1600
0x00
Off
Nominal
range
400.0
'0000.1100.1000.0 000'
0x0C80
3200
401.0
'0000.1100.1000.1 001'
0x0C89
3209
0x42
On
Overrange
425.0
'0000.1101.0100.1 001'
0x0D49
3401
≥ 426.0
'0111.1111.1111.1 010'
0x7FFA
32762
0x60
On
Overflow
1)
Status bits: X= not used, F= error, Ü= overflow