70 Commissioning
WAGO I/O System 750
750-482/000-001 2AI 4-20mA HART NAMUR NE43
Manual
Version 1.0.2
coupler/controller, for the “DP slave address” in the new view.
Confirm your entry by clicking
[Close].
11. Use the mouse to select the communications DTM in the tree structure and
right click on
Configuration
in the context menu.
A dialog window opens with three registers:
Device Information
,
Module
Configuration
, and
Parameterization
.
Figure 22: Dialog Window 750-333 Configuration, Register Device Information
12. Select the register
Module Configuration
and identify for Slot(2) ... Slot(x)
which module is physically plugged in to its fieldbus node. Pay attention to
all I/O modules that deliver process data in the process image.
Slot(1) has been predefined with the fieldbus coupler/controller.
For module configuration, a drop down menu of all available I/O modules
can be found in the
Module
column.
After the node configuration is complete, confirm by clicking
[Apply].