WAGO I/O SYSTEM 750 XTR
Appendix 63
750-481/040-000 2AI RTD Ex i XTR
Manual
Version 1.1.0
8
Appendix
8.1
Configuration and Parameterization using a GSD
File with PROFIBUS DP and PROFINET IO
Requirement
Requirements for parameterization of the I/O module 750-481/040-000 (2AI RTD
Ex i XTR) per GSD file is use of a fieldbus coupler:
•
PROFIBUS DP 750-333(/040-000): > Firmware Version 19
•
PROFIBUS DP 750-833(/0xx-000): > Firmware Version 18
•
PROFINET IO 750-375(/025-000): > Firmware Version 01
•
PROFINET IO 750-377(/025-000): > Firmware Version 01
Behavior after Overwriting with WAGO-I/O-
CHECK
!
If WAGO-I/O-
CHECK
is used to overwrite a parameterization made with the GSD
file, the I/O module operates with the WAGO-I/O-
CHECK
settings until the
750-333/040-000 Fieldbus Couplers are restarted.
After restart, the I/O module is re-parameterized via PROFIBUS using the GSD
settings.
8.1.1
2AI RTD Ex i Configuration
8.1.1.1 PROFIBUS DP Fieldbus Couplers/Controllers
750-333(/0xx-000), 750-833(/0xx-000)
When using the aforementioned PROFIBUS DP fieldbus devices, the process
image size is configured by selecting the corresponding GSD entry.
Table 38: PROFIBUS DP Configuration
GSD Entry
PI Length/[Byte]
Data Type
Inst.
Module
Sub-
Module
I
O
750-481 2AI/RTD/Ex i
n/a
4
n/a
INT16
2
750-481 2AI/RTD/Ex i, PRM
750-481 2AI/RTD/Ex i RA, PRM
6
6
{UINT8, INT16}
750-481 2AI/RTD/Ex i RA
PFC 750-481 2AI/RTD/Ex i
*)
n/a
n/a
n/a
n/a
*)
Only available with 750-833(/0xx-000)