Use in Hazardous Environments
WAGO-I/O-SYSTEM 750 XTR
750-468/040-000 4AI 0-10V DC S.E. /XTR
Manual
Version 1.3.0
Pos : 65.13 / Serie 750 ( WAG O-I/ O-SYST EM)/Ei ns atz i n Ex-Bereic hen/ Beispi elbedruc kung und Text detail N EC 505_2017 @ 29\ mod_1497865583500_21. doc x @ 424739 @ @ 1
Figure 17: Text Detail
– Marking Example for Approved Ex i I/O Module According to NEC 505
Table 24: Description of Marking Example for Approved Ex i I/O Module According to NEC 505
Marking
Description
CI I,
Explosion protection group
Zn 2
Area of application
AEx
Explosion protection mark
nA
Type of protection
[ia Ga]
Type of protection and equipment protection
level (EPL): Associated apparatus with intrinsic
safety circuits for use in Zone 20
IIC
Group
T4
Temperature class
Gc
Equipment protection level (EPL)
Pos : 65.14 / Serie 750 ( WAG O-I/ O-SYST EM)/Ei ns atz i n Ex-Bereic hen/ Beispi elbedruc kung und Text detail N EC 506_2017 @ 29\ mod_1497865583656_21. doc x @ 424742 @ @ 1
Figure 18: Text Detail
– Marking Example for Approved Ex i I/O Module According to NEC 506
Table 25: Description of Marking Example for Approved Ex i I/O Modules According to NEC 506
Marking
Description
CI I,
Explosion protection group
Zn 2
Area of application
AEx
Explosion protection mark
nA
Type of protection
[ia IIIC]
Type of protection and equipment protection
level (EPL): Associated apparatus with intrinsic
safety circuits for use in Zone 20
IIC
Group
T4
Temperature class
Gc
Equipment protection level (EPL)