WAGO-I/O-SYSTEM 750
Use in Hazardous Environments 49
750-461 2AI Pt100/RTD
Manual
Version 1.4.1
Pos: 36.13 /Serie 750 (WAGO-I/O-SYSTEM)/Einsatz in Ex-Bereichen/Beispielbedruckung und Textdetail NEC 505_2017 @ 29\mod_1497865583500_21.docx @ 424739 @ @ 1
Figure 18: Text Detail – Marking Example for Approved Ex i I/O Module According to NEC 505
Table 36: Description of Marking Example for Approved Ex i I/O Module According to NEC 505
Marking
Description
CI I,
Explosion protection group
Zn 2
Area of application
AEx
Explosion protection mark
nA
Type of protection
[ia Ga]
Type of protection and equipment protection
level (EPL): Associated apparatus with intrinsic
safety circuits for use in Zone 20
IIC
Group
T4
Temperature class
Gc
Equipment protection level (EPL)
Pos: 36.14 /Serie 750 (WAGO-I/O-SYSTEM)/Einsatz in Ex-Bereichen/Beispielbedruckung und Textdetail NEC 506_2017 @ 29\mod_1497865583656_21.docx @ 424742 @ @ 1
Figure 19: Text Detail – Marking Example for Approved Ex i I/O Module According to NEC 506
Table 37: Description of Marking Example for Approved Ex i I/O Modules According to NEC 506
Marking
Description
CI I,
Explosion protection group
Zn 2
Area of application
AEx
Explosion protection mark
nA
Type of protection
[ia IIIC]
Type of protection and equipment protection
level (EPL): Associated apparatus with intrinsic
safety circuits for use in Zone 20
IIC
Group
T4
Temperature class
Gc
Equipment protection level (EPL)