![WAGO 750-458 Manual Download Page 93](http://html1.mh-extra.com/html/wago/750-458/750-458_manual_868439093.webp)
Appendix 93
750-458 8AI; TC; Adjust
Manual
Version 1.3.0
10
Appendix
10.1 Configuration and Parameterization using a GSD
File with PROFIBUS DP and PROFINET IO
10.1.1 Configuration 8 AI TC
10.1.1.1 PROFIBUS DP Fieldbus Coupler/Controller
750-333(/0xx-000), 750-833(/0xx-000)
When using the aforementioned PROFIBUS DP fieldbus devices, the process
image size is configured by selecting the corresponding GSD entry.
Table 51: Configuration PROFIBUS DP
GSD Entry
PI-Length/[byte]
Data Type
Inst.
Module
Submodule
I
O
750-458 8AI/TC
n/a
16
n/a
INT16
8
750-458 8AI/TC RA
24
24
{UINT8, INT16}
PFC 750-458 8AI/TC
n/a
n/a
n/a
n/a
10.1.1.2 PROFINET IO Fieldbus Coupler
750-370, 750-375(/025-000), 750-377(/025-000)
When using the aforementioned PROFINET IO fieldbus couplers, the process
image size is configured by selecting the corresponding GSD entry.
Table 52: Configuration 750-370
GSD Entry
PI-Length/[byte]
Data Type
Inst.
Module
Submodule
I
O
750-458 8AI, TC
n/a
16
n/a
INT16
8
75x-458 8AI, TC, EM
24
24
{UINT8, INT16}
Table 53: Configuration 750-375(/025-000), 750-377(/025-000)
GSD Entry
PI-Length/[byte]
Data Type
Inst.
Module
Submodule
I
O
750-458 8AI, TC
INT16[8] I
16
n/a
INT16
8
{UINT8, INT16}[8] I/O
24
24
{UINT8, INT16}