32 Process Image
WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
Manual
Version 1.2.0
4.3
Process Data
4.3.1
Overview of Sensor Types
The following table serves as an overview for all of the supported sensor types
with representation in a standard format and in the S5-FB250 format. The
following sections provide detailed information about the individual sensor types,
arranged by ID. The information provided in the specific tables on the resolution
of the measured data and the raw values ranges yielded from this is based on
manufacturer scaling.
Table 25: Process Data – Overview of Standard Format and S5-FB250 Format
ID
Sensor
type
Standar
d
Measuring range
View
Two's complement/
Amount sign
S5-FB250 Format
Resolu-
tion
Raw value
range
Resolu-
tion
Raw value
range
0
Pt100
IEC 751 −200 °C … 850 °C
0.1 °C
−2000 … 8500
0.5 °C −400 … 1700
1
Ni100
DIN
43760
−60 °C … 250 °C
0.1 °C
−600 … 2500
0.5 °C
−120 … 500
2
Pt1000
IEC 751 −200 °C … 850 °C
0.1 °C
−2000 … 8500
0.5 °C −400 … 1700
3
Pt500
IEC 751 −200 °C … 850 °C
0.1 °C
−2000 … 8500
0.5 °C −400 … 1700
4
Pt200
IEC 751 −200 °C … 850 °C
0.1 °C
−2000 … 8500
0.5 °C −400 … 1700
5
Ni1000
TK6180
DIN
43760
−60 °C … 250 °C
0.1 °C
−600 … 2500
0.5 °C
−120 … 500
6
Ni120
Minco
−80 °C … 260 °C
0.1 °C
−800 … 2600
0.5 °C
−160 … 520
7
Ni1000
TK5000
(
Staefa)
−60 °C … 250 °C
0.1 °C
−600 … 2500
0.5 °C
−120 … 500
8
Ni1000
TK6180
DIN
43760
−50 °C … 150 °C
0.01 °C
−5000 … 15000
0.05 °C −1000 … 3000
9
Ni1000
TK5000
(
Staefa)
−50 °C … 150 °C
0.01 °C
−5000 … 15000
0.05 °C −1000 … 3000
10
Pt1000
IEC 751
−50 °C … 150 °C
0.01 °C
−5000 … 15000
0.05 °C −1000 … 3000
11
Pt100 *
IEC 751
−50 °C … 150 °C
0.01 °C
−5000 … 15000
0.05 °C −1000 … 3000
12
Reserved for expansions
13
Potentiometer
–
0 % … 100 %
0.005 %
0 … 20000
0.05 %
0 … 2000
14
Resistance
measurement
range 1
–
0 Ohm … 5 kOhm 0.2 Ohm
0 … 25000
4 Ohm
0 … 1250
15
Resistance
measurement
range 2
–
0 Ohm … 1.2 kOhm 0.05 Ohm
0 … 24000
0.5 Ohm
0 … 2400
*
Firmware versions
0
2 and above
Observe special features for diagnostics functions!
Note the special features for using the diagnostics functions given in the
"Diagnostics" section.