750-425 [2 DI DC 24 V 3.0 ms NAMUR] 

•  7 

 

 

View 

WAGO-I/O-SYSTEM 750 
I/O Modules 

2 I/O Modules 

2.1  Digital Input Modules 

2.1.1  750-425 [2 DI DC 24 V 3.0 ms NAMUR] 

2-Channel Digital Input Module NAMUR 
Proximity Sensor acc. DIN EN 50227 

2.1.1.1 View 

01 03

+ +

-

-

13 14

C

D

B

A

02 04

750-425

+

DI 2

Power jumper contacts

Data contacts

Status DI 2

24V

0V

Status DI 1

DI 1

Error DI 2

Error DI 1

Uv2

Uv1

 

Fig. 2.1.1-1: 2-Channel Digital Input Module 750-425 

g042500e

 

2.1.1.2 Description 

The digital input 750-425 receives control signals from NAMUR proximity 
sensors (acc. to DIN 19234 and DIN 50227) from the field side. 

The module is a 2-conductor device and has two input channels. Two 
2-conductor proximity sensors may be directly connected to signal input DI 1 
and Uv1 or signal input DI 2 and Uv2. Each sensor can be supplied separately 
over the outputs U

V

1 and U

V

2 with a short circuit proof 8.2 V voltage. 

Each input module has an RC noise rejection filter with a time constant of 
3.0 ms. 

The status of the input channels is indicated via status LEDs. In addition, a red 
error-LED will show if there are any short circuit to ground or a line break in 
either channel. 

In case of a short circuit or a line break one error bit (bit 2 or bit 3) is assigned 
to every channel in the input data process image. By means of this bit the 
supervisory control can detect the error. 
After the error has been eliminated, the error bit in the input process image is 
reset and the error LED goes out. 

Summary of Contents for 750-425

Page 1: ...Fieldbus Independent I O Modules 2 DI DC 24 V 3 0 ms NAMUR 750 425 Manual Version 1 0 3...

Page 2: ...571 8 87 5 55 Fax 49 0 571 8 87 85 55 E Mail support wago com Every conceivable measure has been taken to ensure the correctness and com pleteness of this documentation However as errors can never be...

Page 3: ...Qualification 4 1 1 3 Intended Use 4 1 2 Symbols 5 1 3 Number Notation 5 1 4 Safety Notes 6 1 5 Scope 6 2 I O Modules 7 2 1 Digital Input Modules 7 2 1 1 750 425 2 DI DC 24 V 3 0 ms NAMUR 7 2 1 1 1 Vi...

Page 4: ...ufacturers are always named without referring to patent rights The existence of such rights can therefore not be ruled out 1 1 2 Personnel Qualification The use of the product detailed in this manual...

Page 5: ...ation ESD Electrostatic Discharge Warning of damage to the components by electrostatic discharge Observe the precautionary measure for handling components at risk Note Routines or advice for efficient...

Page 6: ...nformation is to be regarded Do not use any contact spray The spray may impair the functioning of the contact area The WAGO I O SYSTEM 750 and its components are an open system It must only be assembl...

Page 7: ...and has two input channels Two 2 conductor proximity sensors may be directly connected to signal input DI 1 and Uv1 or signal input DI 2 and Uv2 Each sensor can be supplied separately over the output...

Page 8: ...t of the internal power jumper contacts is 10 A When configuring the system it is important not to exceed the maximum sum current However if such a case should occur another supply module must be adde...

Page 9: ...consumption typ internal 5 mA Nominal voltage DC 24 V 15 20 Sensor supply UV DC 8 2 V Signal voltage 0 1 2 mA Signal voltage 1 2 1 mA Input filter 3 0 ms Switching hysteresis 0 2 mA Open circuit volt...

Page 10: ...EEx nA II T4 Conformity Marking More Information Detailed references to the approvals are listed in the document Overview Approvals WAGO I O SYSTEM 750 which you can find on the CD ROM ELECTRONICC Too...

Page 11: ...750 425 2 DI DC 24 V 3 0 ms NAMUR 11 Process image WAGO I O SYSTEM 750 I O Modules...

Page 12: ...WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastra e 27 D 32423 Minden Phone 05 71 8 87 0 Fax 05 71 8 87 1 69 E Mail info wago com Internet http www wago com...

Reviews: