176 Appendix
WAGO-I/O-SYSTEM 750
750-375 PROFINET IO advanced Fieldbus Coupler
Manual
Version 1.1.0
Table 123: Parameterization DO, DIA – Attribute "Diagnosis: Line break"
Attribute Name
Attribute Value
Description
Diagnosis: Line break
0 (false)
A line break on the respective signal channel does
not lead to transmission of a diagnostic alarm nor
to entry in the diagnostics database of the station
proxy.
1 (true)
Provided that the channel diagnostics of the
respective signal channel has been activated, a line
break leads to transmission of a diagnostic alarm
and entry in the diagnostics database of the station
proxy.
14.2.4
PROFIenergy Submodules (DO, PE)
When configuring PROFIenergy submodules, an additional parameter data set is
sent to the data se number or index 0x5000 or 20480.
Regarding the PROFIenergy properties, the following attributes can also be
specified during parameterization.
Table 124: Parameterization – Overview of Additional Attributes for PROFIenergy Submodules
(DO, PE)
Additional Attributes for PROFIenergy Submodules (DO, PE)
-
Minimal pause time (additionally)
-
Pause output state (additionally)
Table 125: Parameterization DO, PE – Attribute "Minimal pause time"
Attribute Name
Attribute Value
Description
Minimal pause time
10 s
Pauses requested by the PROFIenergy profile are
only introduced during pause times greater than or
equal to the setting made. If a PROFIenergy
submodule has been configured from the station
proxy, the setting made here for the respective
output module has no meaning.
1 min
10 min
1 h
10 h
1 d
infinite
Table 126: Parameterization DO, PE – Attribute "Pause output state"
Attribute Name
Attribute Value
Description
Pause output state
0 (false)
If the requested pause time of the PROFIenergy
"Start_Pause" command is greater than or equal to
the parameterized "Minimum pause time", the
respective output channel outputs status '0'.
1 (true)
If the requested pause time of the PROFIenergy
"Start_Pause" command is greater than or equal to
the parameterized "Minimum pause time", the
respective output channel outputs status '1'.