54 • Fieldbus Coupler
Fieldbus Coupler 750-346
WAGO-I/O-SYSTEM
750
DeviceNet
3.1.6 Configuration Software
To enable a connection between the PLC and the fieldbus devices, the inter-
face modules have to be configured with the individual station data.
To this effect, the scope of delivery of WAGO-I/O-SYSTEM 758 includes the
WAGO
NETCON
software intended for design and configuration, start-up and
diagnosis.
Further configuration software of different manufacturers include, for in-
stance, RSNetWorx.
3.1.7 Starting up DeviceNet Fieldbus Nodes
This chapter shows the step-by-step procedure for starting up a
WAGO DeviceNet fieldbus node.
Attention
This description is given as an example and is limited to the execution of a
local start-up of an individual DeviceNet fieldbus node.
The procedure contains the following steps:
1. Connecting the PC and fieldbus node
2. Setting the MAC ID and baud rate
Configuration with static Assembly
3.1.7.1 Connecting the PC and Fieldbus Node
1. Connect the fitted DeviceNet fieldbus node to the DeviceNet fieldbus PCB in
your PC via a fieldbus cable.
The 24 V field bus supply is fed by an external fieldbus network power supply
over the connections V+, V- of the 5-pin fieldbus connector (MCS Series 231).
2. Start your PC.
3.1.7.2 Setting the MAC ID and Baud Rate
3. Use the DIP switches 1...6 to set the desired node address (MAC ID). The bina-
ry significance of the individual DIP switches increases according to the switch
number.
DIP switch
Value
1
2
0
2
2
1
3
2
2
4
2
3
5
2
4
ON
12
34
5
ON
67
8
8
7
6
5
4
3
2
1
g012550x
Fig. 3-10: Example: Setting the
MAC ID 4 (DIP 3 = ON).
6
2
5