88
Commissioning
WAGO I/O SYSTEM 750 XTR
750-333/040-000 FC PROFIBUS G2 12MBd XTR
Manual
Version 1.4.0
The arrangement and meaning of the module information in the process images
depends on the following settings:
•
Process of the configuration check on the part of the station proxy
Parameter Station proxy:
“Start-up if expected and actual configuration
differ”
Setting options:
“disabled”, “enabled”
•
Physical existence of a configured I/O module
Parameter Module slot:
“I/O module is physical”
Setting options:
“plugged in”, “(optional1) not plugged”
• In the case of setting “(optionally) not plugged”, the
“Available I/O module”
plays a role
Cases:
“Configured I/O module”,
“Reserve module”
•
Depiction of diagnostics information in the process image
Parameter Module slot:
“Map diagnostics in input PAB”
Setting options:
“disable”, “enable”
1)
Applies to activating “Start-up if expected and actual configuration differ”
For reasons of clarity, the following combinations are defined for the first three
settings:
Table 39: Parameters
– Settings
Parameter
Settings
Start-up for preset
configuration unlike
actual configuration
I/O module is physical Available I/O module
PK1
not relevant
plugged in
Configured I/O module
PK2
disabled
not plugged
No I/O module
PK3
enabled
optional not plugged
Configured I/O module
PK4
enabled
optional not plugged
Reserve module
PK5
not relevant
plugged in
Configured I/O module
PK6
disabled
not plugged
No I/O module
PK7
enabled
optional not plugged
Configured I/O module
PK8
enabled
optional not plugged
Reserve module
More information about the identifier bytes
A description of the identifier bytes for the fieldbus coupler and I/O modules can
be found in the “Identifier Bytes” chapter in the appendix.