WAGO I/O SYSTEM 750 XTR
Appendix 213
750-333/040-000 FC PROFIBUS G2 12MBd XTR
Manual
Version 1.4.0
12.3.2.6 Parameters of the Up/Down Counters
The table shows the parameterization properties of the up/down counters.
Table 165: Parameter of the up/down counters (CNT)
CNT
Representatives of the CNT:
75x-404, 75x-633, 75x-638
Parameterization data length in bytes
Standard parameterization
Structured parameterization
4
8
Parameter
Settings
Description
Scope
Terminal is physically
The I/O module process data is
Module
(optionally) not plugged
•
(optionally) set to zero or filtered by the
fieldbus coupler.
plugged
*)
•
processed by the I/O module.
Diagnosis
1)
The diagnostic information of the corresponding
channel is
Channel
disabled
*)
•
not transmitted to the PROFIBUS DP
master.
enabled
•
transmitted to the PROFIBUS DP master.
*)
Default settings
1)
Only applies to 75x-633
12.3.2.7 Parameters of the 2-Channel Pulse Width Output Module
The table shows the parameterization properties of the 2-channel pulse width
output module.
Table 166: Parameters of the 2-channel pulse width output module (PWM)
PWM
Representatives of the PWM:
75x-511
Parameterization data length in bytes
Standard parameterization
Structured parameterization
8
12
Parameter
Settings
Description
Scope
Terminal is physically
The I/O module process data is
Module
(optionally) not plugged
•
(optionally) set to zero or filtered by the
fieldbus coupler.
plugged
*)
•
supplied by the I/O module or output to the
periphery.
Substitute value
-32767
… 0
*)
… 32767
or 0
*)
…
32767
If, in the event of a PROFIBUS DP fault, the
switching of substitute values is enabled, within
the fieldbus coupler parameterization, this value is
transmitted to the periphery in the event of a fault.
Channel
*)
Default settings