12.3.2
Parameters of the I/O Modules
12.3.2.1 Parameters of the Digital Input Modules
The table shows the parameterization properties of the 1, 2, 4, 8 and 16-channel
digital input modules without asynchronous diagnostic properties.
Table 153: Parameters of the 1, 2, 4, 8 and 16-channel digital input modules (DI)
1DI_1PI-DIA, 2DI, 4DI, 8DI, 16DI
Representatives of the 1DI_1PI-DIA:
75x-435,
Representatives of the 2DI
:
75x-400, 75x-401, 75x-405, 75x-406, 75x-410,
75x-411, 75x-412, 75x-413, 75x-416, ´75x-427,
75x-429, 75x-438,
Representatives of the 4DI
:
75x-402, 75x-403, 75x-408, 75x-409, 75x-414,
75x-415, 75x-422, 75x-423, 75x-424, 75x-428,
75x-432, 75x-433, 75x-440, 75x-1420, 75x-1421,
75x-1422, 75x-1423,
Representatives of the 8DI
75x-430, 75x-431, 75x-434, 75x-436, 75x-437,
75x-1415, 75x-1416, 75x-1417, 75x-1418,
Representatives of the 16DI
:
750-1400, 750-1402, 75x-1405, 75x-1407
Parameterization data length in bytes
Standard parameterization
Structured parameterization
3
7
Parameter
Settings
Description
Scope
Terminal is physical
The I/O module process data is
Module
(optionally) not plugged
•
(optionally) set to zero from by the fieldbus
coupler.
plugged
*)
•
supplied by the I/O module.
*)
Default settings
The table shows the parameterization properties of the 2-channel digital input
modules with asynchronous diagnostic properties.
Table 154: Parameters of the 2-channel digital input modules (DI_DIA)
2DI_2DIA, 2DI_2PI-DIA,
2DI_2DIA_2ACK, 2DI_2PI-DIA_2ACK
Representatives of 2DI_2DIA respectively
2DI_2PI-DIA
:
75x-419, 75x-421, 75x-425,
Representatives of 2DI_2DIA_2ACK respectively
2DI_2PI-DIA_2ACK
:
75x-418
Parameterization data length in bytes
Standard parameterization
Structured parameterization
3
7
Parameter
Settings
Description
Scope
Terminal is physicaly
The I/O module process data is
Module
(optionally) not plugged
•
(optionally) set to zero by the fieldbus
coupler.
plugged
*)
•
supplied by the I/O module.
Map diagnosis to input PI
1)
The diagnostic information of the I/O module is
Module
disabled
*)
•
not mapped into the input process image.
enabled
•
mapped into the input process image.
Diagnosis
The diagnostic information of the corresponding
channel is
Channel
disabled
*)
•
not transmitted to the PROFIBUS DP
master.
enabled
•
transmitted to the PROFIBUS DP master.
*)
Default settings
1)
Only applies to “*”-modules, e.g. *75x-419
12.3.2.2 Parameters of the Digital Output Modules
The table shows the parameterization properties of the 2, 4, 8 and 16-channel
digital output modules without asynchronous diagnostic properties.