108 Diagnostics
WAGO I/O SYSTEM 750 XTR
750-333/040-000 FC PROFIBUS G2 12MBd XTR
Manual
Version 1.4.0
Table 57: Diagnostics
Designation
Length in
the
diagnostics
frame
Additional information
PROFIBUS DP
standard
diagnostics
Station status 1
1 Byte
See EN 61158
Station status 2
1 Byte
See EN 61158
Station status 3
1 Byte
See EN 61158
DP master address
1 Byte
Station address of the
parameterization master.
Manufacturer ID
2 Byte
ID number of the device
assigned by the PNO.
PROFIBUS DP-
extended
diagnostic
structures
Identifier-related diagnostics
2
… 9 Byte
Existence and length
parameterizable in the
diagnostic buffer.
Device status
7 Byte
Always available in the
diagnostic buffer.
Module status
5
… 20 Byte
Existence and length
parameterizable in the
diagnostic buffer.
Channel-specific diagnostics
each 3 Byte
Exist when the corresponding
event occurs and the message
was sent as part of the
parameterization.
Status messages
each 8 Byte
Exist when the corresponding
event occurs and the message
was sent as part of the
parameterization.
iPar server notification
20 Byte
Temporarily available in the
diagnostic buffer when using
individually parameterizable
modules.