74 Function Description
WAGO-I/O-SYSTEM 750
750-325 CC-Link Fieldbus Coupler
Manual
Version 2.0.1
7.2.2.2 Remote I/O Area
The remote I/O area for digital data is divided into the user-defined area and
system area as shown below.
The following example table shows the data area of the remote I/Os for
CC-Link V1.1 and identical for CC-Link V2.0 at the setting of one cycle.
In the table below, "m" denotes the register number assigned to each remote
device, and "n" denotes the last register number for the number of occupied
points.
The highest register number for CC-Link V1.1 and identical for CC-Link V2.0 at
the setting of one cycle is:
n = (2 * No. of occupied stations) - 1.
The highest register number for CC-Link V2.0 at the setting of several cycles is:
n = (2 * No. of occupied stations * No. of cycles) - (No. of 1).