54 Device Description
WAGO-I/O-SYSTEM 750
750-325 CC-Link Fieldbus Coupler
Manual
Version 2.0.1
Output process image
For 1, 2, 3, 4 station addresses:
RY (digital outputs):
V1.1: 16, 48, 80, 112 bits
V2.0: 16, 48, 80, 112 bits (1 cycle)
16, 80, 144, 208 bits (2 cycles)
48, 176, 304, 432 bits (4 cycles)
112, 368, 624, 880 bits (8 cycles)
and each 16 bits system area
RWw (analog outputs):
V1.1: 4, 8, 12, 16 words (16 bits)
V2.0: 4, 8, 12, 16 words (1 cycle)
8, 16, 24, 32 words (2 cycles)
16, 32, 48, 64 words (4 cycles)
32, 64, 96, 128 words (8 cycles)
*)
Factory setting
4.5.3
Supply
Table 23: Technical Data – Supply
Power source
only be powered from a SELV power
source (Safety Extra Low Voltage)
Voltage via power jumper contacts
24 V DC (-25 % ... +30 %)
Current via power jumper contacts
max
.
10 A DC
Input current
typ.
at rated load (24 V)
600 mA
Efficiency of power supply
typ.
at
nominal load
90 %
Internal current consumption
200 mA at 5 V
Total current for I/O modules
1800 mA at 5 V
Overvoltage category
II
Isolation
500 V system/supply
4.5.4
Accessories
Table 24: Technical Data – Accessories
Miniature WSB Quick marking system
4.5.5
Connection Type
Table 25: Technical Data – Field Wiring
Wire connection
CAGE CLAMP
®
Cross section
0.08 mm² … 2.5 mm², AWG 28 … 14
Stripped lengths
8 mm … 9 mm / 0.33 in