148 I/O Modules
WAGO-I/O-SYSTEM 750
750-325 CC-Link Fieldbus Coupler
Manual
Version 2.0.1
10.2.51 Type 52 - Up/down counter 32 bits
Occupied input process image [(channel x) bits]:
(1x) 48
Occupied output process image [(channel x) bits]: (1x) 48
Items that use this mapping type:
0750-0633#01, 0750-0633#02
Data mapping:
I/Q
Byte
Bit
Data Type
Contents
I
0
0
BOOL
Status clock
I
0
1
BOOL
Status up/down
I
0
2
BOOL
Status out
I
0
4
BOOL
Status block counter
I
0
5
BOOL
Status set counter
I
0
6
BOOL
General Error Bit
I
2
WORD
Actual count value Low Word
I
4
WORD
Actual count value High Word
Q
0
0
BOOL
Control out depending from counter
Q
0
2
BOOL
Control out
Q
0
4
BOOL
Control block counter
Q
0
5
BOOL
Control set counter
Q
2
WORD
Set value Low Word
Q
4
WORD
Set value High Word
10.2.52 Type 53 - Frequency Counter type 2
Occupied input process image [(channel x) bits]:
(1x) 48
Occupied output process image [(channel x) bits]: (1x) 48
Items that use this mapping type:
0750-0633#03
Data mapping:
I/Q
Byte
Bit
Data Type
Contents
I
0
0
BOOL
Ack. Frq. Meas. Range
I
0
1
BOOL
Ack. Frq. Meas. Range
I
0
2
BOOL
Status out
I
0
4
BOOL
Tvd Acknowledge
I
0
5
BOOL
Status Gate input
I
0
6
BOOL
General Error Bit
I
2
WORD
Frequency Low Word
I
4
WORD
Frequency High Word
Q
0
0
BOOL
Frequency measuring range
Q
0
1
BOOL
Frequency measuring range
Q
0
2
BOOL
Control out
Q
0
4
BOOL
Tvd Request
Q
2
WORD
Watchdog Time