WAGO-I/O-SYSTEM 750
I/O Modules 145
750-325 CC-Link Fieldbus Coupler
Manual
Version 2.0.1
10.2.48 Type 48 - DC Drive Controller
Occupied input process image [(channel x) bits]:
(1x) 48
Occupied output process image [(channel x) bits]: (1x) 48
Items that use this mapping type:
0750-0636, 0750-0636/0000-0700, 0750-0636/0000-0800
Data mapping:
I/Q
Byte
Bit
Data Type
Contents
I
0
0
BOOL
moving negative
I
0
1
BOOL
moving positive
I
0
2
BOOL
On target
I
0
3
BOOL
busy
I
0
4
BOOL
standstill
I
0
5
BOOL
reference ok
I
0
6
BOOL
error, see extended info
I
1
0
BOOL
preset input enabled
I
1
1
BOOL
optimize on (and Z-Input for 750-636 > FW2)
I
1
2
BOOL
extended info on
I
1
3
BOOL
PWM active
I
1
4
BOOL
current control on
I
1
5
BOOL
preset input
I
1
6
BOOL
limit switch negative
I
1
7
BOOL
limit switch positive
I
2
0
BOOL
over temperature warning
I
2
0
WORD
actual position low word
I
2
1
BOOL
over temperature
I
2
2
BOOL
overflow warning
I
2
3
BOOL
24V ok
I
2
4
BOOL
overload
I
2
5
BOOL
motion detection timeout
I
2
6
BOOL
parameter write failed
I
2
7
BOOL
24VL Ok (only 750-636/000-800)
I
3
0
BOOL
24VM Ok (only 750-636/000-800)
I
4
0
WORD
actual position high word
Q
0
0
BOOL
move negative
Q
0
1
BOOL
move positive
Q
0
2
BOOL
positioning
Q
0
3
BOOL
preset
Q
0
4
BOOL
current control on
Q
1
0
BOOL
preset input enable
Q
1
1
BOOL
optimize on
Q
1
2
BOOL
extended info on
Q
1
7
BOOL
error quit
Q
2
0
WORD
target position low word
Q
4
0
WORD
target position high word