10.2.36 Type 36 - DALI/DSI master module
Occupied input process image [(channel x) bits]:
(1x) 48
Occupied output process image [(channel x) bits]: (1x) 48
Items that use this mapping type:
0750-0641
Data mapping:
I/Q
Byte
Bit
Data Type
Contents
I
0
0
BOOL
Transmit accepted
I
0
1
BOOL
Receive request
I
0
2
BOOL
Init accepted
I
0
3
BOOL
Actor Error
I
0
4
BOOL
Frame Error
I
0
5
BOOL
Bus Error
I
0
6
BOOL
General Module Error
I
1
0
BYTE
DALI Response
I
2
0
BYTE
DALI Address
I
3
0
BYTE
Message 3
I
4
0
BYTE
Message 2
I
5
0
BYTE
Message 1
Q
0
0
BOOL
Transmit request
Q
0
1
BOOL
Receive accepted
Q
0
2
BOOL
Init request
Q
1
0
BYTE
DALI Command, DSI dimming value
Q
2
0
BYTE
DALI Address
Q
3
0
BYTE
Parameter 2
Q
4
0
BYTE
Parameter 1
Q
5
0
BYTE
Command extension