10.2.19 Type 17 - Incremental encoder interface type 2
Occupied input process image [(channel x) bits]:
(1x) 48
Occupied output process image [(channel x) bits]: (1x) 48
Items that use this mapping type:
0750-0634
Data mapping:
I/Q
Byte
Bit
Data Type
Contents
I
0
0
BOOL
Latch value set
I
0
1
BOOL
D2/3/4 = Cycle duration
I
0
2
BOOL
Counter Set Acknowledge
I
0
3
BOOL
Counter Underflow
I
0
4
BOOL
Counter Overflow
I
1
BYTE
Counter value Low Byte
I
2
BYTE
Counter value High Byte
I
3
0
BYTE
Cycle duration byte 2 (MSB)
I
4
WORD
Latch value / Cycle duration Lo-Word
Q
0
0
BOOL
Release Index Pulse
Q
0
1
BOOL
Read cycle time
Q
0
2
BOOL
Counter Set
Q
1
BYTE
Set value Low Byte
Q
2
BYTE
Set value High Byte