124 I/O Modules
WAGO-I/O-SYSTEM 750
750-325 CC-Link Fieldbus Coupler
Manual
Version 2.0.1
10.2.13 Type 11 - Digital output; Diagnostics type 1
Occupied input process image [(channel x) bits]:
(1x) 4
Occupied output process image [(channel x) bits]: (1x) 4
Items that use this mapping type:
0750-0506
Data mapping (for symmetrical channels, only the first channel is specified):
I/Q
Byte
Bit
Data Type
Contents
I
0
0
BOOL
Channel 1 Diagnostic bit 0
I
0
1
BOOL
Channel 1 Diagnostic bit 1
I
0
2
BOOL
Channel 2 Diagnostic bit 0
I
0
3
BOOL
Channel 2 Diagnostic bit 1
Q
0
0
BOOL
Digital output 1
Q
0
1
BOOL
Digital output 2
10.2.14 Type 12 - Digital output; Diagnostics type 2
Occupied input process image [(channel x) bits]:
(2x) 1
Occupied output process image [(channel x) bits]: (2x) 1
Items that use this mapping type:
0750-0507, 0750-0508, 0753-0508, 0750-0508/0040-0000, 0750-0522,
0750-0532, 0750-0537, 0753-0537, 0750-0539
Data mapping (for symmetrical channels, only the first channel is specified):
I/Q
Byte
Bit
Data Type
Contents
I
0
0
BOOL
Diagnostic bit
Q
0
0
BOOL
Digital output