WAGO-I/O-SYSTEM 750
Device Description
17
750-1504 16DO 24V DC 0.5A
s: 26 /Serie 750 (WAGO-I/O-SYSTEM)/Gerätebeschreibung/Anschlüsse/Leistungskontakte/Feldversorgung - Überschrift 3 @ 6\mod_1256294692864_21.doc @ 43664 @ 3 @ 1
Po
3.2.2
Power Contacts/Field Supply
Po
s: 27.1 /Serie 750 (WAGO-I/O-SYSTEM)/Wichtige Erläuterungen/Sicherheitshinweise/Vorsicht/Vorsicht: Verletzungsgefahr durch scharfkantige Messerkontakte! @ 6\mod_1256193279401_21.doc @ 43414 @ @ 1
Risk of injury due to sharp-edged male contacts!
The male contacts are sharp-edged. Handle the module carefully to prevent injury.
s: 27.2 /Serie 750 (WAGO-I/O-SYSTEM)/Gerätebeschreibung/Anschlüsse/Leistungskontakte 2 LK (Messer/Feder) @ 7\mod
Po
_1266317883167_21.doc @ 50688 @ @ 1
The I/O module 750-1504 has 2 self-cleaning power jumper contacts that supply
and transmit power for the field side. The contacts on the left side of the I/O
module are designed as male contacts and the contacts on the right side as spring
contacts.
Table 4: Power jumper contacts
Connection
Type
Number
Function
1 Blade
contact
2
Infeed of the field
supply voltage
(U
V
and 0 V)
1
2
1
2
Figure 3: Power
jumper contacts
2 Spring
contact
2
Forwarding of the
field supply voltage
(U
V
and 0 V)
Po
s: 27.3 /Serie 750 (WAGO-I/O-SYSTEM)/Wichtige Erläuterungen/Sicherheitshinweise/Achtung/Achtung: Maximaler Strom Leistungskontakte 10 A @ 3\mod_1226499143500_21.doc @ 25029 @ @ 1
Do not exceed maximum current via power contacts!
The maximum current to flow through the power contacts is 10 A.
Greater currents can damage the power contacts.
When configuring the system, ensure that this current is not exceeded. If
exceeded, an additional potential feed module must be used.
s: 27.4 /Serie 750 (WAGO-I/O-SYSTEM)/Wichtige Erläuterungen/Sicherheitshinweise/Hinweis/Hinweis: Potentialeinspeiseklemme für Erde einsetzen! @ 3\mod_1226499037468_21.doc @ 25023 @ @ 1
Po
Use potential feed module for Ground (earth)!
The I/O module has no power contacts for PE intake and transfer. Use a potential
feed module when a PE feed is needed for the subsequent I/O modules.