2789-9080
Fieldbus Description
26
| Version: 1.1.0
Communication Module IO-Link
Table 40: Enable switching DO on/off via process data
Bit 4
IODD Value
Description
1
active
enabled
0
inactive
disabled
Digital output on
The DO is controlled if “Enable switching DO on/off via process data” is enabled.
Table 41: Digital output on
Bit 5
IODD Value
Description
1
active
enabled
0
inactive
disabled
Inverted settings
Bit 10 determines whether inverted or non-inverted settings are used.
Table 42: Inverted settings
Bit 10
IODD Value
Description
0
Non-inverted
normal, not inverted
1
Inverted
inverted
4.2.4.10 System/General (Index 445)
Behavior on application of power
Bits 0 to 2 determine the behavior with applied voltage.
Table 43: Behavior on application of power
Bit 0
1
Bit 1
1
Bit 2
1
IODD Value
Description
1
0
0
Restore previous state
Restore previous state
0
1
0
DC output switched on
DC output switched on
0
0
1
DC output remains switched off
DC output remains switched off
1) Bits 0, 1 and 2 must be mutually locked (at least one bit must be set).
Activate switch-on delay
Bit 3 enables or disables the switch-on delay.
Table 44: Activate switch-on delay
Bit 3
IODD Value
Description
1
active
enabled
0
inactive
disabled
Activate key lock
Bit 6 enables or disables the key lock.
Table 45: Activate key lock
Bit 6
IODD Value
Description
1
active
enabled
0
inactive
disabled