2789-9023
Fieldbus Description
Product manual | Version: 1.0.0
39
EtherNet/IP Communication Module
Status Messages
Table 45: Events and Measured Values – Status Messages
Attribute ID
Access
Data type
Description
2
Get
UINT16
Bit 0
DC status OK
Bit 1
Overtemperature
Bit 2
No output voltage
Bit 3
Short circuit at output
Bit 4
Status at digital input
Warnings
Table 46: Events and Measured Values – Warnings
Attribute ID
Access
Data type
Description
3
Get
UINT16
Bit 0
Undervoltage at out-
put
Bit 1
Overvoltage at out-
put
Bit 2
Overload
Bit 3
Configurable over-
load threshold ex-
ceeded
Bit 4
Configurable operat-
ing hours reached
Bit 5
TopBoost output
Bit 6
PowerBoost output
Bit 7
Higher device tem-
perature
Bit 8
-
Error
Table 47: Events and Measured Values – Errors
Attribute ID
Access
Data type
Description
4
Get
UINT16
Bit 0
Overtemperature,
device switched off
Bit 1
No output voltage
Bit 2
Short circuit at output
Bit 3
Circuit breaker
tripped