2789-9023
Fieldbus Description
Product manual | Version: 1.0.0
33
EtherNet/IP Communication Module
General Device Parameters
Table 30: General Device Parameters – Modbus
Attribute ID
Access
Data type
Description
122
Get/Set
UINT16
Device address
124
Get/Set
UINT32
Baud rate
This parameter can be used to set the baud rate. The op-
tions are as follows:
Value
Baud Rate
4800
4800 baud
9600
9600 baud
19200
19200 baud
38400
38400 baud
57600
57600 baud
115200
115200 baud
230400
230400 baud
560800
560800 baud
126
Get/Set
UINT16
Data bits
The options are as follows:
Value
Data Bit
0
7
1
8
127
Get/Set
UINT16
Stop bits
The options are as follows:
Value
Stop Bit
0
1
1
0.5
2
2.5
3
1.5
128
Get/Set
UINT16
Parity
The options are as follows:
Value
Parity
0
None
1
Even
2
Odd
129
Get/Set
UINT16
Response delay (unit: ms)
130
Get/Set
UINT16
Data format
The options are as follows:
Value
Data Format
0
Big-endian (B0, B1, B2, B3)
1
Middle-endian (B2, B3, B0,
B1)
2
Little-endian (B3, B2, B1,
B0)
4.2.7.2 Device Parameters of the WAGO Pro 2 Power Supply
The following parameters of the WAGO Pro 2 Power Supply can be edited via the prod-
uct.