2789-9023
Properties
16
Product manual | Version: 1.0.0
EtherNet/IP Communication Module
3.6 Indicators
The product has a visual status indicator. This indicator consists of six LEDs.
LNK/ACT2
SPEED1
LNK/ACT1
COM OK
ERR
SPEED2
Figure 4: Visual Status Indicator
Table 2: Operating Status Indication
Indicator
LED Description
State
Description
ERR
Error
Off
Ready for operation; no error
On
General error/system error
Flashing (8 Hz)
EtherNet/IP connection error
Flashing (16 Hz) Communication module is resetting to factory
defaults
COM OK
Device status
Off
No connection to lower-level device
On
Initialization
Flashing (2 Hz)
Communication active
Flashing (16 Hz) IP address is being assigned via DHCP
LNK/ACT1
Port 1: connection/activity
Off
No connection present
On
Connection present, but no activity
Flashing
Connection and activity present
SPEED1
Port 1: speed
Off
Connection rate: 10 Mbit/s
On
Connection rate: 100 Mbit/s
LNK/ACT2
Port 2: connection/activity
Off
No connection present
On
Connection present, but no activity
Flashing
Connection and activity present
SPEED2
Port 2: speed
Off
Connection rate: 10 Mbit/s
On
Connection rate: 100 Mbit/s
3.7 Control Elements
A reset button is located on the front of the product. This button can be used to reset the
product.
See
8
for a detailed description of how you can use
the reset button to make settings.
3.8 Technical data
3.8.1 Product
Table 3: Technical Data – Product
Property
Value
Width
35 mm
Height
80 mm