2787-2154
Properties
Product manual | Version: 1.0.2
23
Power Supply Pro 2
3.9.8 Environmental Conditions
Table 27: Technical Data ‒ Environmental Conditions
Property
Value
Surrounding air temperature, operation
−25 … +70 °C
Surrounding air temperature, restricted operation
1)
−40 … −25 °C
Surrounding air temperature, storage
−40 … +85 °C
Derating (temperature-dependent)
2)
−3 %/K (> +60 °C)
Derating (location-dependent)
2)
−17.5 %/1000 m (> +60 °C; 2000 m or higher)
Relative humidity
5 … 96 % (no condensation permissible)
Elevation above sea level, max.
5000 m
Overvoltage category
III (≤ 2000 m)
II (> 2000 m)
Vibration according to IEC 60068-2-6
5 … 150 Hz / 1g
Shock according to IEC 60068-2-27
15 g / 11 ms
Pollution degree according to IEC/EN 60664-1
2
1)
Without mechanical actuation of buttons, female connectors etc., for example
2)
See section
8
Note
Observe the following for long-term storage:
For long-term storage, power must be applied to equipment with built-in capacitors for
five minutes at least every two years.
3.9.9 Product Protection
Table 28: Technical Data – Product Protection
Property
Value
Internal input fuse
1)
T 6.3 A / 250 VAC
Transient suppression at input
Yes, varistor
Overload protection at output
Electronic
Overvoltage protection at output, max.
2)
60 VDC
Feedback voltage, max.
3)
Yes, max. 60 V
Degree of protection
IP20
Ingress protection against foreign objects
> 4 mm
Overtemperature protection
4)
Yes
Circuit breaker of the nominal current circuit
5)
16 A (for USA/Canada: 15 A)
1)
Used only as an AC fuse. An external DC fuse must be used with DC supply.
2)
Internal limitation via a second control loop, deactivation of power supply, automatic restart
3)
The voltage must not be exceeded due to power feedback.
4)
Configurable; see section
8
“Latching Shutdown on Thermal Overload” Mode [
5)
The circuit breaker can be used for activation during installation. In this case, the circuit breaker must meet
all the requirements on this shutdown device. If an additional switch is used, it must have the same electrical
load capacity as the circuit breaker.
3.9.10 Security
Table 29: Technical Data – Safety
Property
Value
Input and output insulation, according to EN 61010-1;
EN 61010-2-201
SELV/PELV
Protection class, with protective wire connection
I