46
Use in Hazardous Environments
WAGO-I/O-SYSTEM 750
753-466 2 AI 4-20 mA S.E.
Manual
Version 1.5.0
Pos: 72.16 /Serie 750 ( WAGO-I/O-SYST EM)/Ei nsatz i n Ex-Bereichen/Beispi elbedruckung und Textdetail C EC_2017 @ 29\mod_1497865583297_21.docx @ 424736 @ @ 1
Figure 32: Text Detail – Marking Example for Approved Ex i I/O Modules According to CEC 18
attachment J
Table 21: Description of Marking Example for Approved Ex i I/O Modules According to CEC 18
attachment J
Marking
Description
Dust
Ex
Explosion protection mark
nA
Type of protection
[ia IIIC]
Type of protection and equipment protection level
(EPL): Associated apparatus with intrinsic safety
circuits for use in Zone 20
IIC
Group
T4
Temperature class
Gc
Equipment protection level (EPL)
X
Symbol used to denote specific conditions of use
Gases
Ex
Explosion protection mark
nA
Type of protection
[ia Ga]
Type of protection and equipment protection level
(EPL): Associated apparatus with intrinsic safety
circuits for use in Zone 0
IIC
Group
T4
Temperature class
Gc
Equipment protection level (EPL)
X
Symbol used to denote specific conditions of use
Pos: 72.17 /D okumentati on allgemei n/Gli ederungsel emente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1