13 Technical data
100_0101_td_0026.fm
29
13.3
Extension cable
Only use permitted extension cables, see chapter
Safety
.
Refer to the following table for the required cross-section area of the extension cable:
Example
You utilize an IEC58 and want to use an extension cable with a length of 25 m.
The machine has an input voltage of 120V 1~.
According to the table, the extension cable must feature a cross-section area of 2.5 mm
2
.
WARNING
Electrical voltage.
Injuries from electrocution.
Check power cable and extension cable for signs of damage.
Only use extension cables for which grounded conductors are connected to
the plug and the coupling (only for machines of class rating I, see chapter
Technical Data
).
NOTES
Refer to the nameplate or the chapter
Technical data
(via the item number) for the type
designation and voltage rating of your machine.
Machine
Voltage
[V]
Extension
[m]
Cross-section area of
cable [mm
2
]
IEC45
120 1~
< 45
1,5
< 75
2,5
< 119
4
IEC58
120 1~
< 18
1,5
< 30
2,5
< 48
4
Machine
Voltage
[V]
Extension
[ft]
Cross-section area of
cable
[AWG]
IEC45
120 1~
< 129
16
< 205
14
< 323
12
IEC58
120 1~
< 52
16
< 82
14
< 129
12