5.6
Output signal adaptation
EOUT (Output signal: READY = OFF)
Command
Parameters
Unit
Group
EOUT_1 x
EOUT_2 x
x= -10000… 10000 0.01 %
BASIC
Output value in case of a detected error or a deactive ENABLE input. A value (degree of valve opening) for
use in the event of a sensor error (or the module is disabled) can be defined here. This function can be used
if, for example, the drive is to move to one of the two end positions (at the specified speed) in case of a
sensor error.
|EOUT| = 0
The output is switched off in the event of an error. This is normal behavior.
CAUTION!
If the output signal is 4… 20 mA, the output is switched off when
|EOUT| = 0
. If a null
value = 12 mA is to be output in the event of an error, EOUT must be set to 1
8
.
The output value defined here is stored permanently (independently of the parameter set). The
effects should be analyzed by the user for each application from the point of view of safety.
Do not use the manual mode in conjunction with the EOUT command. After the deactivation of
the HAND input the output is set to the EOUT value.
8
This is necessary if using valves without error detection for signals lower than 4 mA. If the valve has an error detection,
it moves into a defined position after switching off the output.