background image

The sauna room and ventilation

Correct ventilation is very important for pleasant sauna baths. The following recommendations are currently in force 
for sauna rooms with electric stoves:

The fresh air ventilator should be placed at least 50 cm above the sauna stove. The exhaust air ventilator should 
be placed as far from the stove as possible and close to the edge of the floor. You can also lead the exhaust air to 
the shower room from under the door to the sauna room (as long as the gap is at least 5 cm high). This alternative 
works well when you use mechanical air conditioning. The diameter of the ventilation pipes should be between 50 
and 100 mm and the exhaust vent should be bigger than the fresh air vent.

Instructions for electrical installations

The sauna stove can only be connected to the power supply by an authorised electrician in accordance with the 
applicable regulations. The connecting cable must be a rubber cable type H07RN-F. Never use a PVC cable in a 
sauna stove! 
Connect the stove semi-permanently to the junction box. The junction box must be splash-proof and it must not be 
installed higher than 50 cm from the floor. The thermostat knob is located in the lower part of the stove. Please see 
pages 10-11.

Additional connections:

1. Connecting the signal light outside the sauna room

The connecting cable must be of type H07RN-F, with the same circumference as the connecting cable of the stove 
(see wiring diagrams on pages 10-11).

   2.Connecting electrical heating with the sauna stove

 

 

Run the control cable for electrical heating directly into the junction box of the sauna stove, and from there to the 
terminal blocks of the sauna stove along a rubber cable with the same thickness as that of the connection wire (see 
wiring diagrams on pages 10-11).

Troubleshooting

If the sauna stove does not heat, check the following:

- Has the power been switched on?
- Has the timer been switched on to a section where the sauna stove should be heated?
- Does the thermostat show a higher figure than the temperature of the sauna?
- Has the timer stopped/got stuck? The timer knob can only move freely if there is a gap of 1-2 mm between the 
timer knob and the front panel of the timer.
- Has the temperature limit control cut the power off? Reset the temperature limit control by pressing the hole next 
to the thermostat knob until you hear a clicking sound. Always check the reason for the overheating before you turn 
the stove back on!

For additional information, please contact your dealer or the manufacturer!

Vuolux Oy warrants its electric sauna stoves for one (1) year from the date of purchase. Please retain the sales 
receipt as you will need it for any warranty service. The warranty is valid only for sauna stoves in private use.

_____________________________________________________________________________________________________

Manufacturer’s contact information:

Vuolux Oy

Pajatie 5

85500 NIVALA

FINLAND

Tel. +358-44-3243100

[email protected]

www.vuolux.fi

5

Summary of Contents for 11400 Kairo Tower

Page 1: ...ER MANUAL FOR VUOLUX ELECTRIC SAUNA STOVE 11400 Vuolux Kairo Tower 6 kW 11800 Vuolux Manhattan Tower 6 kW 11440 Vuolux Kairo Tower 8 kW 11840 Vuolux Manhattan Tower 8 kW 11460 Vuolux Kairo Tower 10 5...

Page 2: ...instructions and directions for use 5 The sauna room and ventilation 5 Instructions for electrical installation 5 Troubleshooting 5 Warranty and contact information 6 8 Safety distances and wiring di...

Page 3: ...tions before you mount the sauna stove Mount the sauna stove on the floor Check the minimum safety distances The safety distances are distances to an inflammable structural element and you can halve t...

Page 4: ...knob to position zero 0 Please make sure that the timer has switched the power off after the selected time You should also check the timer after thunderstorms ________________________________________...

Page 5: ...s the connecting cable of the stove see wiring diagrams on pages 10 11 2 Connecting electrical heating with the sauna stove Run the control cable for electrical heating directly into the junction box...

Page 6: ...um safety distances see picture below The safety distance is measured from the widest deepest highest point MIN SAUNA 5 m B 1000 400V 3N 6kW IP X4 120 A 120 1900 C D 170 640 E F MIN mm E E 300 MAX 3 A...

Page 7: ...e 10A Output resistor 2 kW __________________________________ Vuolux 8 0 Output 8 kW Voltage 400 V 3N Connecting cable 5 x 2 5 S Fuse 16A Output resistor 2 7 kW __________________________________ Vuol...

Page 8: ...S Fuse 10A _____________________________________ Vuolux 8 0 Output 8 kW Voltage 400 V 3N Connecting cable 5 x 2 5 S Fuse 16A _____________________________________ Vuolux 10 5 Output 10 5 kW Voltage 4...

Reviews: