VULCANIC 9030-02 Owner'S Manual Download Page 1

VULCANIC S.A. - 48, rue Louis Ampère

Zone Industrielle des Chanoux - F 93330 NEUILLY / MARNE  (France)

Tél. (33) 01.49.44.49.20 - Fax (33) 01.49.44.49.41

OWNER’S MANUAL

LIQUID DILATATION THERMOSTAT

REFERENCE 9030 - 02/03

1 - 

APPLICATION  :

Temperature regulation or limitation for liquids, gases or solids.

2 - 

DESCRIPTION  :

-

Liquid dilatation thermostat with bulb and capillary of copper for reference 9030-02 and stainless steel for 
reference 9030-03.

-

Potential-free inverter contact.

-

Breaking capacity : 16 A / 400 VAC.

-

Maximum operating voltage : 400 V.

-

Differential : 2.5% of full scale.

-

Connection by 6.35 Faston terminals.

-

Façade mounting or on support (inside case or box for instance).

REFERENCE

Range

Bulb Ø

Bulb L

Capillary length

(°C)

(mm)

(mm)

(mm)

9030 - 02

 0 +100 

6

160

1000

9030 - 03

 +50 +300 

6

90

1000

3 - 

PRECAUTIONS  FOR  USE  :

-

Handle the capillary with care. It must never be pierced as this could cause the final destruction of the equipment.  
Allow a forming radius in excess of 5 mm.

-

Check that the material of the bulb and capillary is compatible with the product being tested in the event of it 
being in direct contact with it.

4 - 

ASSEMBLY  AND  ELECTRICAL  CONNECTION  :

4 - 1 - ASSEMBLY :

-

On the support which will be receiving the thermostat (façade or attaching lug), form an 7 mm Ø hole 
for accommodating the shaft of the knob and two 4 mm Ø holes (diametrically opposed) on a 22 mm Ø 
radius centered on the shaft of the knob, ensuring that the equipment is turned as required (see diagram 
below).

-

Insert the shaft of the knob in the hole provided for the purpose.

-

Place the pierced tightening washer on the support receiving the equipment then install the dial, making 
sure it is properly aligned.

-

Install the two attaching screws.

UT 9030 - 02/03 - A - Issued 04/03/98

1/3