Vortex iStat6 User Manual Download Page 9

 

  Controls User Manual 

– HPAH

 

 

Rev_20200811 

Page  9 of 9 

Table 4 Admin Mode 

Line 1 

Line 2 

Set. 

Type 

Description 

Default 

HP AirH 

#### 

Display 

Display status of system 

NO CALL 

W1_Aux 

(0)Off/(1)On 

Input 

Thermostat auxiliary heating W1 (ON/OFF) 

  

W2_Aux 

(0)Off/(1)On 

Input 

Thermostat auxiliary heating W2 (ON/OFF) 

 

Y1_HP 

(0)Off/(1)On 

Input 

Thermostat heat pump Y1 (ON/OFF) 

  

Y2_HP 

(0)Off/(1)On 

Input 

Thermostat heat pump Y2 (ON/OFF) 

 

SA_TMP 

###.# C 

Input 

Supply air temperature 

  

RA_TMP 

###.# C 

Input 

Return air temperature (display only, not used) 

  

FAN_Spd 

#### % 

calc 

Fan speed as a percentage 

  

ContFan 

#### % 

  

Setting 

Continuous Fan airflow as a percent of maximum. 

50 

HPH1Fan 

#### % 

  

Setting 

Heat pump heating 1

st

 stage fan speed as a % of max. 

50 

HPH2Fan 

#### % 

  

Setting 

Heat pump heating 2

nd

 stage fan speed as a % of max. 

100 

HPC1Fan 

#### % 

  

Setting 

Heat pump cooling 1

st

 stage fan speed as a % of max. 

50 

HPC2Fan 

#### % 

  

Setting 

Heat pump cooling 2

nd

 stage fan speed as a % of max. 

100 

Aux1Fan 

#### % 

  

Setting 

Auxiliary heating 1

st

 stage fan speed as a % of max. 

50 

Aux2Fan 

#### % 

  

Setting 

Auxliiary heating 2

nd

 stage fan speed as a % of max. 

100 

HP Pre 

#### sec 

  

Setting 

Time fan runs at half speed at beginning of heat pump 
call in seconds 

10 

HP Post 

#### sec 

  

Setting 

Time fan runs at half speed at the end of a heat pump 
call in seconds 

30 

Aux Pre 

#### sec 

  

Setting 

Time fan runs at half speed at beginning of auxiliary heat 
call in seconds 

30 

AuxPost 

#### sec 

  

Setting 

Time fan runs at half speed at the end of auxiliary heat 
call in seconds 

30 

PumpExr 

(0)Off/(1)On 

  

Input 

Daily pump exerciser ON/OFF 

OFF 

HP_2STG 

(0)Off/(1)On 

  

Text 

Setting 

Is the heat pump 2 stage? 

HP2Time 

#### min 

  

Setting 

Time to activate 2nd stage cooling in minutes. 

20 

FrzTemp 

#### C 

  

Setting 

Freeze alarm setpoint temperature 

FrzDly1 

#### min 

  

Setting 

Freeze Delay 1 - wait time to activate freeze alarm 

FrzDly2 

#### min 

  

Setting 

Freeze Delay 2 - wait time to restore operation after a 
freeze alarm 

HPAH 

##.## REV 

Input 

Program name and revision number 

2.00 

Modbus 

#### 

  

Setting 

Modbus address 

137 

 

 

 

 

 

Summary of Contents for iStat6

Page 1: ...ols User Manual HPAH and DXAH Heat pump air handler with iStat6 electronic controller Vortex Source Systems Cambridge Ontario Phone 888 781 8151 Fax 888 670 2544 info vortexsource com www vortexsource...

Page 2: ...Controller Basics 3 Table 1 Status Messages 3 Table 2 Display Icons 3 Controller Keypad 4 USER MODE 4 ADMIN MODE 4 Initial Controls Setup 5 Cycle Timer Pump Exerciser 5 Two Stage Heat Pump 6 Freeze Pr...

Page 3: ...stem Table 1 provides a list of the different possible status messages and their meaning There are also a number of small icons that may appear around the edges of the display according to the current...

Page 4: ...below USER MODE This is the basic display and operating mode in which only a limited selection of parameters may be displayed Refer to Table 3 for a description of each item displayed ADMIN MODE This...

Page 5: ...f each heat pump cycle Default is 10 seconds This can improve comfort by pre heating cooling the coil HP Post Length of time in seconds that the fan will run at half speed at the end of each heat pump...

Page 6: ...le delay intervals FrzDly1 sets the amount of time the supply air temperature has to remain below FRZ_TMP before the alarm is triggered and FrzDly2 sets the amount of time until the compressor is allo...

Page 7: ...control has failed No Auxiliary Heating Try Test Mode first pushing the button on the bottom underneath of the control will run the auxiliary pump and fan for 20 seconds Pipes should get warm and fan...

Page 8: ...N This usually occurs when there is inadequate airflow for a given system Ensure that the air filter is not plugged and all ductwork is open Ensure supply air temperature sensor is located after cooli...

Page 9: ...ooling 2nd stage fan speed as a of max 100 Aux1Fan Setting Auxiliary heating 1st stage fan speed as a of max 50 Aux2Fan Setting Auxliiary heating 2nd stage fan speed as a of max 100 HP Pre sec Setting...

Reviews: