IR610 high performance vector control frequency inverter user manual Chapter 5 function code table
- 76 -
the parameter to avoid wrong operation.
P06.31
Terminal protection
function
0
:
no protection
When command is terminal ,power on and
terminal effective,inverter will run
1
:
protection
When command is terminal ,power on and
terminal effective, inverter will not run ,so need
terminal ineffective then effective,then inverter
will run
0
★
P06.32
DI terminal on/ready time
0.000s
~
30.000s
1.000s
★
P06.33
VDI1 source
To Select the source of VDI1, Please select the
input signal of VDI1 together with the Unit’s digit
of P06.17.
06.00
★
P06.34
VDI 2 source
To Select the source of VDI2, Please select the
input signal of VDI1 together with the Ten’s digit
of P06.17.
06.00
★
P06.35
VDI 3 source
To Select the source of VDI3, Please select the
input signal of VDI1 together with the Hundred’s
digit of P06.17.
07.00
★
P06.36
VDI 4 source
To Select the source of VDI4, Please select the
input signal of VDI1 together with the Thousand’s
digit of P06.17.
44.00
★
07 Group Multi-function Digital output
r07.00
DO output port status
Define as per bit,
0:ineffective 1:effective
Bit0:DO1 Bit1:D02 Bit2:relay1, Bit 3:relay 2
Bit4: DO3;Bit5: DO4 Bit6: DO5; Bit7: DO6
Bit8: VDO1;Bit9: VDO2
-
●