This function is mostly used in textile and chemical industry and some application such as traversing and winding so
it is used for balancing the workload allocation when multiple motors are used to drive the same load. The output
frequency of the frequency inverters decreases as the load increases. You can reduce the workload of the motor
under load by decreasing the output frequency for this motor, implementing workload balancing among multiple
motors.
P01.44 or P01.46=0,This function disable
Start acceleration
Deceleration stop
Frequency
swing center
Frequency swing
lower limit
Frequency swing range:AW-set the frequency(choose
P01.43)*P01.44 Kick-hop frequency:jw-aw*P01.45
+A
w
-Aw
Frequency swing
cycle (P01.46)
Triangle wave rise time:
P01.47*frequency swing
cycle
Running
command
Frequency
swing limit
Output frequency
Jw
Jw
P01.48
Auxiliary frequency
effective threshold
When the main frequency ≥ this setting, the
auxiliary frequency will be effective
0.00Hz
☆