IR610 high performance vector control frequency inverter user manual Chapter3 Product appearance and wiring
- 27-
IR610-280G/315PT4
M12
35
150
×
2
M12
15
120
IR610-315G/355PT4
M12
35
150
×
2
M12
15
150
IR610-355G/400PT4
M12
35
150
×
2
M12
15
150
IR610-400G/450PT4
M12
35
185
×
2
M12
15
185
IR610-450G/500PT4
M12
35
150
×
3
M12
35
185
IR610-500G/560PT4
M12
35
150
×
3
M12
35
185
IR610-560G/630PT4
M12
35
185
×
3
M12
35
240
IR610-630GT4
M12
35
185
×
3
M12
35
240
IR610-710GT4
M12
35
185
×
3
M12
35
240
3.2.4
Cautions for Main Circuit Wiring
(
1
)
Power Supply Wiring
◆
It is forbidden to connect the power cable to the output terminal of the inverter. Otherwise, the internal
components of the inverter will be damaged.
◆
In order to provide input side overcurrent protection and power outage overhaul convenience, the inverter should
be connected to the power supply through circuit breakers and contactors.
◆
Please confirm the power phase, the voltage is consistent with the product nameplate, do not match may result
in damage to the inverter.
(
2
)
DC wiring
◆
Do not connect the braking resistor directly to +, -, which may cause the inverter to be damaged or
even fire.
◆
When using the external brake unit, pay attention to +, - can not be reversed, otherwise it will cause
damage to the inverter and brake unit or even cause a fire.
(
3
)
Motor Wiring
◆
It is forbidden to short circuit or ground the inverter output terminal, otherwise the internal components
of the inverter will be damaged.
◆
Avoid short circuit the output cables or with the inverter enclosure, otherwise there exists the danger of
electric shock.
◆
It is forbidden to connect the output terminal of the inverter to the capacitor or LC/RC noise filter with
phase lead, otherwise, the internal components of the inverter may be damaged.
◆
When contactor is installed between the inverter and the motor, it is forbidden to switch on/off the
contactor during the running of the inverter, otherwise, there will be large current flowing into the
inverter, triggering the inverter protection action.
◆
Length of cable between the inverter and motor
Summary of Contents for IR610 Series