Appendix A Modbuscommunication protocol IR610 high performance vector control frequency inverter user manual
- 170 -
Command code
1byte
0x90
Abnomal Code
1byte
See Abnormal response
information
A.3.4 Commad code 0x08Diagnostic function
Modbus Command Code 0x08 Providea series of tests to check the communication system
between the client (master) device and the server (slave) or various internal error conditions in the
server.
This function uses the sub-command code of 2 bytes inquery to define the type of test to be
performed. The server copies the command and subcommand codes in the normal response.
Some diagnostics cause the remote device to return the data through the normally responding data
fields.
Diagnostic functions to remote devices generally do not affect the user program running in the
device. The main diagnostic function of this product is not line diagnosis (0000), used to test the
host from the machine is normal communication.
Request PDU
Command code
1byte
0x08
Subcommand code
2byte
0x0000
~
0xFFFF
Data
2byte
0x0000
~
0xFFFF
Respond PDU
Command code
1byte
0x08
Subcommand code
2byte
0x0000
Data
2byte
Same as request of PDU
Wrong PDU
Command code
1byte
0x88
Abnomal code
1byte
See Abnormal response
information
A.4 Abnormal response information
When the master device sends a request to the slave device, the master expects a normal
response. The master's query may result in one of four events:
(1) If the slave device receives a request for a communication error and the query can be
processed normally, the slave device will return a normal response.
(2) If the slave device does not receive the request due to a communication error, no