Where it is not possible to place the alarm on the ceiling, 
the smoke alarm may be installed on the wall at a minimum 
of 300mm and a maximum of 500mm off the ceiling at the 
junction of the wall.

There are special requirements for stairways, sloping ceilings 
and ceilings with exposed beams. Specific requirements are 
explained in the relevant Building Regulation.

    

¬

This Voltex Smoke Alarm is designed for use in 

residential dwellings. It is intended to detect smoke 

before it reaches the sleeping occupants of a 

building. The ensuing alarm is designed to wake the 

occupants and give them time to evacuate the building. 

 

    

¬

This smoke alarm SHALL be installed in accordance 

with national and local council building regulations 

and the latest edition of the Australian and New 

Zealand wiring Rules AS/NZS 3000. Building codes 

and regulations may vary from each state jurisdiction. 

 

    

¬

The smoke alarm incorporates a non-replaceable 

battery which is manufactured to power the 

smoke alarm for at least 10 years without being 

recharged subject to normal  use and regular 

maintenance from the date of manufacture. 

To reduce the likelihood of nuisance alarms, do not install a 

smoke alarm near cooking appliances, in bathroom, laundry 

room, or close to heating and cooling supply vents. 

Do not install a smoke alarm in dusty or dirty areas.

Do not install a smoke alarm where bugs or insects are 

present.

NOTE: Recently the wireless paring signal has changed. You
will ONLY be able to pair alarms marked with this symbol
        on the inner box and sticker on rear of product.
Please contact Voltex on 1300 722 275 in case of needing to
pair with an earlier version.

    

¬

At least one smoke alarm shall be fitted on each storey       

(including basements) - in each bedroom and in corridors       

or hallways which connect bedrooms and the rest of 

the dwelling or as required by relevant local legislation.  

 

 

    

¬

Where practicable smoke alarms should be placed on 

the ceiling.    

 

    

¬

It is important to install the smoke alarm in the centre 

of the room, avoiding dead air spaces (an area in which       

trapped hot air will prevent smoke from reaching the 

alarm). Smoke alarms must not be placed within: 

 

 

 

 

 

 

 

    

¬

Smoke alarms must be paired (interconnected) with       

every other smoke alarm so they all activate together 

 

300mm of a corner of a ceiling and a wall

 

300mm of a light fitting

 

400mm of an air-conditioning vent

 

400mm of the blades of a ceiling fan 

Important Safety Information

Recommended locations

Nuisance Alarms

Recommended Installation Locations

SAS115BW SMOKE ALARM

USER MANUAL

Congratulations on purchasing a Voltex Smoke Alarm.

Please read these instructions carefully before installation 

and operation.

AS 3786

:

2014

Sensing Type

Photoelectric (Type A - contains

no radioactive material)

Power Supply

Non-replaceable 10 Year Lithium

Battery

Interconnectivity

Wireless (433.42MHz)

Wireless range

Up to 100m in open space

Interconnection

Maximum 40 paired alarms

Size

114mm x 38mm

Temp range

0°C - 45°C

Max Humidity

5%-95%RH

Alarm Signal Pattern ISO 8201

Alarm Volume

85dB at 3m

Hush Time

10 mins

Compliance

AS 3786:2014

Certification

CSIRO Verification Service

II301020-AZ